Local solution of 14 bus network with scaled demands. --------------- Modifications -------------- voltage constraints: load buses: [0,1.05] generator buses: [0.95,1.05] Demands: 3.5*PD Relax generator bounds and only consider linear costs Objective Function Value = 25860.86 $/hr ================================================================================ | Bus Data | ================================================================================ Bus Voltage Generation Load Lambda($/MVA-hr) # Mag(pu) Ang(deg) P (MW) Q (MVAr) P (MW) Q (MVAr) P Q ----- ------- -------- -------- -------- -------- -------- ------- ------- 1 1.050 0.000* 135.27 77.32 - - 20.000 - 2 1.050 -0.368 687.81 282.42 75.95 12.70 20.000 - 3 0.950 -33.527 0.00 244.42 329.70 19.00 29.113 - 4 0.798 -16.618 - - 167.30 -3.90 24.538 2.140 5 0.832 -15.332 - - 26.60 1.60 24.287 1.837 6 0.950 -47.275 0.00 241.74 39.20 7.50 26.291 - 7 0.501 8.382 - - - - 27.124 -7.336 8 0.950 68.710 234.98 378.47 - - 40.000 - 9 0.518 -31.787 - - 103.25 16.60 21.564 0.559 10 0.563 -39.705 - - 31.50 5.80 24.358 1.477 11 0.741 -45.206 - - 12.25 1.80 26.083 1.013 12 0.867 -51.906 - - 21.35 1.60 28.675 0.385 13 0.817 -51.753 - - 47.25 5.80 29.721 1.451 14 0.539 -55.318 - - 52.15 5.00 35.615 5.082 -------- -------- -------- -------- Total: 1058.06 1224.37 906.50 73.50