Local solution of 14 bus network. --------------- Modifications -------------- voltage constraints: load buses: [0,1.05] generator buses: [0.95,1.05] Relax generator bounds and only consider linear costs ================================================================================ | Bus Data | ================================================================================ Bus Voltage Generation Load Lambda($/MVA-hr) # Mag(pu) Ang(deg) P (MW) Q (MVAr) P (MW) Q (MVAr) P Q ----- ------- -------- -------- -------- -------- -------- ------- ------- 1 1.011 0.000* 95.36 76.52 - - 20.000 - 2 1.006 -0.338 322.34 200.00 21.70 12.70 20.000 0.003 3 0.950 -12.706 0.00 120.10 94.20 19.00 22.683 - 4 0.776 -8.695 - - 47.80 -3.90 22.768 2.425 5 0.812 -10.166 - - 7.60 1.60 22.948 1.725 6 0.950 -43.621 -0.00 366.76 11.20 7.50 23.617 - 7 0.508 -13.906 - - - - 23.572 0.607 8 1.050 -13.906 0.00 323.01 - - 23.572 - 9 0.044 -74.414 - - 29.50 16.60 18.805 -9.088 10 0.147 -56.536 - - 9.00 5.80 31.508 7.099 11 0.529 -45.058 - - 3.50 1.80 24.885 2.104 12 0.861 -45.894 - - 6.10 1.60 24.292 -0.164 13 0.780 -45.287 - - 13.50 5.80 24.953 1.205 14 0.292 -57.089 - - 14.90 5.00 33.487 5.569 -------- -------- -------- -------- Total: 417.70 1086.39 259.00 73.50